NIST Rhode Island Nightclub Fire Investigation Team Calls For Improvements

Date:
March 10, 2005
Source:
National Institute Of Standards And Technology
Summary:
The Commerce Department’s National Institute of Standards and Technology (NIST) is calling on the organizations that develop building and fire safety codes, standards and practices—and the state and local agencies that adopt them—to make specific changes to improve the fire safety of nightclubs as a result of the agency’s investigation of the Feb. 20, 2003, fire at The Station nightclub in W. Warwick, R.I.

Computer model of fire at The Station nightclub showing the temperature variation after 90 seconds at 1.5 meters (5 feet) above the floor.
Credit: Image courtesy of National Institute Of Standards And Technology

PROVIDENCE, R.I. — The Commerce Department’s National Institute of Standards and Technology (NIST) today called on the organizations that develop building and fire safety codes, standards and practices—and the state and local agencies that adopt them—to make specific changes to improve the fire safety of nightclubs as a result of the agency’s investigation of the Feb. 20, 2003, fire at The Station nightclub in W. Warwick, R.I.

Recommendations for changes in nightclubs include requiring sprinklers, tighter restrictions of the use of flammable materials in finish products, and improved means of egress in emergencies. Other recommendations address emergency preparedness and response practices as well as a call for more research to better understand the way people behave in emergency situations such as fires.

All 12 recommendations, contained within the draft report released today for public comment at a press briefing in Providence, are based on the findings of the NIST investigation into the fire that claimed 100 lives. To prevent additional deaths, injuries and property loss in the future, the recommendations call for:

* requiring the installation of sprinkler systems in all new and existing nightclubs regardless of size;

* tightening restrictions for nightclubs on the use of flammable materials as a finish product (such as a wall covering) and further limiting the use of pyrotechnics;

* allowing for more rapid evacuation from nightclubs by changing egress requirements (for example, increasing the capacity of the main exit to accommodate, at a minimum, two-thirds of the maximum permitted number of occupants);

* eliminating the practice of “grandfathering” older nightclubs from new or revised safety regulations;

* requiring redundancy in passive and active fire protection systems for nightclubs;

* considering and incorporating insight gained from similar past building failures when analyzing proposed changes to model codes for nightclubs;

* increasing the number of portable fire extinguishers required in nightclubs;

* implementing more effective fire inspection programs for nightclubs as guided by the model codes;

* ensuring that career and volunteer fire departments meet standards for staffing, equipment, communications systems and major incident/mass casualty incident operating procedures;

* conducting research to better understand human behavior in emergency situations and to predict the impact of building design on safe egress in emergencies;

* conducting research to better understand fire spread and suppression; and

* conducting research to develop and refine computer models and computer-aided decision tools with which communities can make cost-effective choices about code changes, fire safety technologies and emergency resource allocations.

Details on these recommendations are found in the accompanying fact sheet.

The NIST report identifies three factors that directly contributed to the rapid spread of the fire, the resulting building failure and the large loss of life at The Station nightclub. These are: (1) the hazardous mix of building contents; (2) an inadequate capability to suppress the fire early; and (3) the inability of exits to handle the egress of all of the occupants in the short time available with such a fast-growing fire.

Key findings in these three areas are detailed in the accompanying fact sheet.

Video taken inside the nightclub by WPRI-TV (Providence, R.I.) and reporting by the Providence Journal assisted the NIST investigation team.

NIST welcomes comments on the report, available at http://www.nist.gov/public_affairs/ncst.htm#draft_report, which are received by April 4, 2005. Comments may be sent via surface mail to The Station Investigation, NIST, 100 Bureau Dr., Stop 8660, Gaithersburg, Md. 20899-8660; via fax to (301) 975-4052; or via e-mail to ncst@nist.gov.

NIST’s investigation of The Station nightclub fire, begun on Feb. 27, 2003, was conducted under the National Construction Safety Team (NCST) Act. The act gives NIST the responsibility for conducting fact-finding investigations of building-related failures that result in substantial loss of life. NIST has no regulatory authority under the NCST Act.

The primary objectives of the NIST Rhode Island nightclub fire investigation were to:

* determine the conditions in the nightclub prior to the fire, such as the materials of construction and contents;

* the location and conditions of doors, windows and ventilation; the installed fire protection systems; the number of occupants and their approximate locations;

* reconstruct the fire ignition, fire spread and survivability within the building using computer models;

* examine the impact on survivability of having an installed sprinkler system, all other conditions being the same; and

* analyze the emergency evacuation and occupant responses to better understand the impediments to safe egress.

As an agency of the U.S. Department of Commerce’s Technology Administration, NIST develops and promotes measurement, standards and technology to enhance productivity, facilitate trade and improve the quality of life.


Story Source:

The above story is based on materials provided by National Institute Of Standards And Technology. Note: Materials may be edited for content and length.


Cite This Page:

National Institute Of Standards And Technology. "NIST Rhode Island Nightclub Fire Investigation Team Calls For Improvements." ScienceDaily. ScienceDaily, 10 March 2005. <www.sciencedaily.com/releases/2005/03/050309121322.htm>.
National Institute Of Standards And Technology. (2005, March 10). NIST Rhode Island Nightclub Fire Investigation Team Calls For Improvements. ScienceDaily. Retrieved July 28, 2014 from www.sciencedaily.com/releases/2005/03/050309121322.htm
National Institute Of Standards And Technology. "NIST Rhode Island Nightclub Fire Investigation Team Calls For Improvements." ScienceDaily. www.sciencedaily.com/releases/2005/03/050309121322.htm (accessed July 28, 2014).

Share This




More Matter & Energy News

Monday, July 28, 2014

Featured Research

from universities, journals, and other organizations


Featured Videos

from AP, Reuters, AFP, and other news services

Europe's Highest Train Turns 80 in French Pyrenees

Europe's Highest Train Turns 80 in French Pyrenees

AFP (July 25, 2014) Europe's highest train, the little train of Artouste in the French Pyrenees, celebrates its 80th birthday. Duration: 01:05 Video provided by AFP
Powered by NewsLook.com
TSA Administrator on Politics and Flight Bans

TSA Administrator on Politics and Flight Bans

AP (July 24, 2014) TSA administrator, John Pistole's took part in the Aspen Security Forum 2014, where he answered questions on lifting of the ban on flights into Israel's Tel Aviv airport and whether politics played a role in lifting the ban. (July 24) Video provided by AP
Powered by NewsLook.com
Creative Makeovers for Ugly Cellphone Towers

Creative Makeovers for Ugly Cellphone Towers

AP (July 24, 2014) Mobile phone companies and communities across the country are going to new lengths to disguise those unsightly cellphone towers. From a church bell tower to a flagpole, even a pencil, some towers are trying to make a point. (July 24) Video provided by AP
Powered by NewsLook.com
Algonquin Power Goes Activist on Its Target Gas Natural

Algonquin Power Goes Activist on Its Target Gas Natural

TheStreet (July 23, 2014) When The Deal's Amanda Levin exclusively reported that Gas Natural had been talking to potential suitors, the Ohio company responded with a flat denial, claiming its board had not talked to anyone about a possible sale. Lo and behold, Canadian utility Algonquin Power and Utilities not only had approached the company, but it did it three times. Its last offer was for $13 per share as Gas Natural's was trading at a 60-day moving average of about $12.50 per share. Now Algonquin, which has a 4.9% stake in Gas Natural, has taken its case to shareholders, calling on them to back its proposals or, possibly, a change in the target's board. Video provided by TheStreet
Powered by NewsLook.com

Search ScienceDaily

Number of stories in archives: 140,361

Find with keyword(s):
Enter a keyword or phrase to search ScienceDaily for related topics and research stories.

Save/Print:
Share:

Breaking News:
from the past week

In Other News

... from NewsDaily.com

Science News

Health News

Environment News

Technology News



Save/Print:
Share:

Free Subscriptions


Get the latest science news with ScienceDaily's free email newsletters, updated daily and weekly. Or view hourly updated newsfeeds in your RSS reader:

Get Social & Mobile


Keep up to date with the latest news from ScienceDaily via social networks and mobile apps:

Have Feedback?


Tell us what you think of ScienceDaily -- we welcome both positive and negative comments. Have any problems using the site? Questions?
Mobile: iPhone Android Web
Follow: Facebook Twitter Google+
Subscribe: RSS Feeds Email Newsletters
Latest Headlines Health & Medicine Mind & Brain Space & Time Matter & Energy Computers & Math Plants & Animals Earth & Climate Fossils & Ruins